46-648 Jupiter Magnetostrictive Transmitters
2.3.2 Status Messages
Display Message Action Comment
OK None Normal operating mode
Initial None Shown at power-up during
self check
TrimReqd Factory set Loop values are defaults, Consult Factory
loop output may be in accurate
Cal Reqd Factory set default calibration parameters Consult Factory
are in use, level reading may be inaccurate
Lo Temp Present temperature in electronics Transmitter may need to be moved
compartment is below -40° F (-40° C) to ensure temperature is within
specification
Hi Temp Present temperature in electronics Transmitter may need to be moved
compartment is above +176° F (+80° C) to ensure temperature is within
specification
Float 2 No level signal detected from float 2 Make sure 2 floats are being used,
Fail are not damaged, and within
measuring range
Float 1 No level signal detected from float 1 Make sure float is not damaged
Fail and within measurement range
No Signal No signal detected from any float Make sure float is not damaged
and within measurement range
LoopFail Loop current differs from expected value Consult Factory
Snsr Brd Measurement board not responding Consult Factory
DfltParm Internal non-volatile parameters have been Consult Factory
reset to default values