6
= Quick Start up
MENU: STEP BY STEP PROCEDURE – Jupiter 200: Level only – Loop signal (PV) is Level
Screen Action Comment
Run modeConfiguration
1
2
3
4
8
11
12
13
*Status*
*
Level*
*%Output*
*Loop*
L
evel
xxx.xx
%Output
xx.xx
Loop
xx.xx mA
5
MeasType
(select)
Set 4mA
xxx.xx
7
Probe Ln
x
xx.xx
6
Units
(select)
1
0
Lvl Ofst
xxx.xx
9
Set 20mA
x
xx.xx
Damping
xx.x s
Fault
(Select)
Poll Adr
xx
Transmitter Display Transmitter default values cycle every 8 seconds. Status «Status»,
V
olume «
V
olume
»
, % Output «
%
Output
»
, and Loop «
L
oop
»
.
Transmitter Display Transmitter displays Level Value in selected engineering units.
T
ransmitter Display
T
ransmitter displays % Output measurement derived from 20 mA
span.
Transmitter Display Transmitter displays Loop measurement (mA).
Select the type of measurement Select level «Lvl only».
Select units for level cm «cm» or inches «inches».
Enter the exact length of
probe
Enter as per the 3 last digits of the probe partnumber on the nameplate:
From 15 cm up to 999 cm
e.g. 242-D111-AAM-280, enter «
280» cm probe length.
Enter the PV for 4 mA Enter 4 mA level point, measured from reference point in selected
level units.
Enter the PV for 20 mA Enter 20 mA level point, measured from reference point in selected
level units.
Enter the offset value
When entering configuration values from the end of the probe is
cumbersome, an of
fset can be introduced to determine a new
reference point. This reference point can be either below the
probe (positive offset) or at the probe (negative offset). See page
5 “Terminology”.
Enter the damping factor. A Damping factor (1-25 seconds) may be added to smooth a noisy
display and/or output due to turbulence.
Below 15 s = 0,1 s increments.
Above 15 s = 1 s increments.
Enter the value for error. Select «3.6 mA», «22 mA» or hold last value «HOLD». In case of
loop failure, error signal will follow the failing trend; meaning the unit
will show 3.6 mA when the reviewed loop current by the device is
found too low. The unit will show 22 mA in case the reviewed loop
current is found too high.
Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single transmitter
installation.